  Where  kitchen  exhaust  operation  or  dryer  exhaust  operation  would  depressurize  the   conditioned  space  with  respect  to  outside  more  than  5  Pa,  then  an  exhaust  make-‐up  air  system   shall  be  installed,  reducing  net  exhaust  flow,  to  reduce  depressurization  due  to  kitchen  exhaust   operation  or  dryer  exhaust  operation  to  less  than  5  Pa.       7.    REFERENCES         ANSI/ASHRAE  Criterion  52.2,  Method  of  Testing  General  Ventilation  Air-‐Cleaning  Devices  for   Removal  Efficiency  by  Particle  Size.         California  Energy  Commission  (2001).  California  Title  24  Standards,  ACM  Manual,  Appendix  F,   Sections  4.3.8.2.1  and  4.3.7.2.     Energy  Star,  Ventilating  Fans  criteria,   http://www.energystar.gov/index.cfm?c=vent_fans.pr_crit_vent_fans     HVI  916,  "HVI  Airflow  Test  Procedure":    (Procedure  that  establishes  uniform  methods  for   laboratory  testing  of  powered  residential  ventilating  equipment  for  airflow  rate.  This   publication  covers  the  test  equipment,  tests  of  specific  HVI  classification  groups,  and  test   reports  for  maintaining  the  standard.)     HVI  920,  "HVI  Product  Performance  Certification  Procedure  Including  Verification  and   Challenge":    (Publication  that  describes  HVI's  certification,  verification,  and  challenge  testing   procedures.)     IECC  Climate  Zone  Map     NFPA  54/ANSI  Z223.1,  National  Fuel  Gas  Code     NFPA  31,  Criterion  for  the  Installation  of  Oil-‐Burning  Equipment     NFPA  211,  Criterion  for  Chimneys,  Fireplaces,  Vents,  and  Solid-‐Fuel  Burning  Appliances  

Articles in this issue

Links on this page

Archives of this issue

view archives of IAQ.net Resources - BSC Standard 01-2013 Ventilation for New Low-Rise Residential Buildings_v2